Fire and life safety shapes the scope of almost every commercial renovation. Moving a wall, adding seats or changing how a space is used can change the exits, fire separations, rated doors, fire alarm and sprinklers the space needs, and in Vancouver those changes decide which permits, trades and engineers the project needs. Sorting them out at the start keeps the drawings, the permit and the budget aligned.

This guide is for business owners, tenants, landlords and property managers planning an office, retail, restaurant, cafe or industrial renovation in Vancouver or elsewhere in Metro Vancouver. It covers how fire and life-safety items shape scope and permits. For keeping neighbouring tenants safe while the work is under way, see our guide to renovating a commercial building while it stays open.

TL;DR

  • In Vancouver, Part 11 of the Building By-law can require fire and life-safety upgrades when an existing building is altered.
  • New walls, rooms and ceilings often mean sprinkler, fire alarm, emergency lighting and exit sign changes, each with its own permit.
  • Fire separations and rated doors only work as complete assemblies, so penetrations, hardware and closers matter as much as the wall.

Why does fire and life safety drive commercial renovation scope?

Most commercial renovations happen inside existing buildings that were designed around a particular layout and use. The exits, fire separations, alarm devices and sprinkler heads were placed for that layout. When a renovation changes the layout or the use, those systems have to be checked against the new plan, and some of them will need to move, change or be upgraded.

Common triggers we see in tenant improvements include:

  • New rooms or walls that block sprinkler coverage, alarm devices or the path to an exit.
  • A dropped or new ceiling that changes sprinkler head locations.
  • More people in the space, such as added seating in a restaurant or a denser office layout, which can change exit requirements.
  • A change of use, for example from storage to office or from office to retail.
  • Combining or splitting suites, which affects the fire separations between tenants.

When does a Vancouver renovation trigger fire and life-safety upgrades?

The City of Vancouver has its own Building By-law. When an existing building is altered, renovated or repaired, or its major occupancy changes, Part 11 can require upgrades. The City's notes to Part 11 set fire upgrade levels from F1 to F4, and the levels are cumulative:

  • F1: exits in the project area, for number, capacity and fire separations.
  • F2: adds alarms and detectors (where existing devices are provided), emergency lights, access to exits, exit signs and exit lights.
  • F3: adds items such as sprinklers and standpipes, flame spread ratings, floor assemblies and occupancy separations.
  • F4: applies upgrades to the entire building.

The level depends on the type and extent of the work, and the designer's code review sets out what applies. Outside Vancouver, the BC Building Code governs alterations, and Burnaby, Surrey, Richmond and other Metro Vancouver municipalities run their own building permits and fire inspections. For the permit side, see commercial building permits in Vancouver.

How do exits and fire separations affect the layout?

Exits are usually the first thing a code review looks at. The number of exits, their capacity and the route to them depend on how many people the space is designed for and how it is used. A new reception wall, a storage room or a row of private offices can lengthen or block a route that worked before, so the layout has to be tested against exit requirements early, not after the walls go up.

Fire separations divide a building into compartments: between tenants, around exit stairs and corridors, and between different occupancies. A separation is a full assembly, not just a wall. It has to run to the right height, use the specified boards and framing, and keep its rating where pipes, ducts and cables pass through it, which is where tested firestop systems come in. Our guides to commercial demising walls and Type X vs regular drywall cover the wall assemblies in more detail.

What do rated doors need?

A door in a fire separation is part of that separation. It needs a fire-protection rating, a rated frame and hardware that lets it close and latch on its own. The BC Fire Code, which Vancouver's Fire By-law adopts with local changes, says closures in fire separations must not be obstructed, blocked, wedged open or altered in a way that stops them from working. If a door needs to stay open for daily use, it needs a hold-open device that meets the building code and releases the door automatically when the fire alarm sounds, not a wedge.

In a renovation, check rated doors early. New access control, a changed swing or a replacement door can all affect the rating and latching, so the door schedule and hardware should be reviewed with the designer before ordering.

What changes for fire alarms and sprinklers?

Fire alarm and sprinkler work is done by qualified trades under their own permits, coordinated with the rest of the renovation:

  • Sprinklers. In Vancouver, a fire sprinkler permit is needed to install a new system or change an existing one, including any change to the piping. A licensed fire sprinkler contractor applies for it, and the permit is only valid once any required building permit is issued. Simple repairs and sprinkler head or valve replacements no longer need a permit. Larger scopes need sealed engineering drawings from a fire protection engineer.
  • Fire alarm. The City's fire alarm bulletin says modifying an existing fire alarm system needs an electrical permit. Where devices are added, wiring is extended, or the zoning or sequence of operation changes, a building permit is also needed, and the system has to be verified to CAN/ULC-S537 after the work.
  • Emergency lighting and exit signs. These follow the new layout and are part of the electrical scope.

Shutdowns need a plan too. In Vancouver, the alarm monitoring company must be told when a fire protection system goes out of service and when it is back. If a system is out for more than 4 continuous hours in a 24-hour period, the fire watch order procedures require notifying the fire department through 3-1-1, and the City requires a fire watch while any part of a fire protection system is not working.

Who is responsible for fire and life-safety design and sign-off?

On a typical commercial renovation, the responsibilities split like this:

  • Architect or designer and code consultant: the code review, exits, fire separations and door schedule.
  • Engineers: fire protection, mechanical and electrical design, including sprinkler and fire alarm drawings where required.
  • Licensed trades: sprinkler, fire alarm and electrical installation under their own permits.
  • General contractor or construction manager: schedules and coordinates the trades and consultants, builds the walls, doors and firestopping to the drawings, and lines up inspections.

Landlords often add their own rules, such as approved fire alarm and sprinkler contractors for base building systems. Check the lease and the landlord's tenant criteria before pricing. Our guide to planning an office tenant improvement covers that step.

How Multigroup Contracting helps

Multigroup Contracting is a commercial general contractor and fee-based construction manager founded in 2016, with our Vancouver office at 700-838 West Hastings St. We are registered with WorkSafeBC and carry $5M in liability insurance. We coordinate the fire and life-safety parts of commercial renovations, working with designers, engineers and licensed sprinkler, fire alarm and electrical trades, and we build the walls, rated doors and firestopping to the drawings. See our tenant improvements, office fit-outs, retail buildouts, coffee shop renovations and commercial construction services.

Tell us about your space and what you plan to change. Get a free quote, call 778-819-5933 or email info@multigroup.ca.

FAQ

Does a commercial renovation trigger fire and life-safety upgrades in Vancouver?

It can. Part 11 of the Vancouver Building By-law sets upgrade levels F1 to F4 based on the work. Lower levels focus on exits and fire separations in the project area; higher levels add alarms, emergency lighting, exit signs and sprinklers, and F4 applies to the entire building.

Do I need a permit to move sprinkler heads in Vancouver?

Usually, yes. A fire sprinkler permit is needed to install or change a sprinkler system, including any change to the piping, and a licensed fire sprinkler contractor applies for it. Simple repairs and sprinkler head or valve replacements do not need one.

What permits does fire alarm work need in a Vancouver tenant improvement?

Fire alarm work needs an electrical permit. If devices are added, wiring is extended, or the zoning or sequence of operation changes, a building permit is also needed, and the system must be verified to CAN/ULC-S537 after the work.

Can fire doors be propped open during a renovation?

No. The BC Fire Code says closures in fire separations must not be obstructed, blocked, wedged open or altered in a way that stops them from working. A fire door may only stay open on a hold-open device that meets the building code.

What happens if the fire alarm or sprinklers are shut down for the work?

In Vancouver, the alarm monitoring company must be told when a fire protection system goes out of service and when it is restored. If it is out for more than 4 continuous hours in a 24-hour period, the fire department must also be notified through 3-1-1, and a fire watch is required.